UltraBreeze: Testing the Thermal / Fire Safety Switch

The Thermal / Fire Safety Switch (the “thermal”) ships in the red bag and plugs into the plug hanging from your UltraBreeze. It holds two parts: a thermal button that closes when the attic is above 75°F, and a fire safety fuse inside the black sleeve.

Tools

  • Multimeter set to ohms (Ω) or continuity

UltraBreeze pin map: fan plug positions 1 and 2 go to the solar panel, 3 and 4 to the motor; on the Thermal / Fire Safety Switch, positions 1 and 4 are the fire safety fuse and 2 and 3 the thermal button

Fan plug: solar panel 1 + 2, motor 3 + 4. Thermal: fire safety fuse 1 + 4, thermal button 2 + 3.

Steps

  1. Unplug the thermal: find the plug hanging from the base of the fan and pull the two black connectors apart. This cuts the solar power to the fan. Pull on the connectors, not the wires.
  2. Fire safety fuse: touch the meter leads to positions 1 and 4 on the thermal's plug. Zero ohms, or a beep, is good at any temperature.
  3. Thermal button: touch the leads to positions 2 and 3. Above 75°F it reads zero or beeps. Below 75°F it reads open (“1” or “OL”), which is normal, so test it when the attic is warm.
  4. If either pair reads open when it should be closed, replace the thermal. See UltraBreeze: Replacing the Thermal / Fire Safety Switch; contact us for a new one.
  5. Plug the thermal back in. Push the connectors together until no metal shows between them.